Indiana Administrative Code (Last Updated: December 20, 2016) |
Title 410. INDIANA STATE DEPARTMENT OF HEALTH |
Article 410IAC6. SANITARY ENGINEERING |
Rule 410IAC6-8.3. Residential On-Site Sewage Systems |
Section 410IAC6-8.3-76. Subsurface trench flood dosed on-site sewage systems: design and construction requirements
-
(a) Subsurface trench flood dosed on-site sewage systems shall meet all of the requirements of:
(1) sections 74 and 75 of this rule; and
(2) this section.
(b) When a subsurface trench flood dosed soil absorption system is used, the dosing effluent pump shall be sized, and its controls set to deliver the DDF to the soil absorption field in each dose. Effluent pump selection shall be based on manufacturer's pump curves for the required discharge rate from Table VII, as follows, at the total head imposed on the pump:
Table VII – Required Effluent Pump Discharge Rates for Subsurface Trench Flood Dosed On-Site Sewage Systems
Number of Bedrooms
Discharge Rate in Gallons per Minute
1
30-35
2
30-35
3
30-45
4
30-60
5
38-75
6
45-90
(c) The total head for a subsurface trench flood dosed soil absorption system shall be the elevation difference between the effluent pump off and the highest point in the force main or the outlet of the effluent force main in the distribution box, whichever is the highest elevation, in addition to the friction loss in the effluent force main expressed in feet.
(d) The effluent force main shall drain unless it is installed below the frost line, as listed in Table VIII, as follows, and designed so that no effluent remains in any portion of the effluent force main located above the frost line:
Table VIII – Frost Penetrations in Indiana (in inches)
Adams
60
Franklin
48
Lawrence
48
Rush
54
Allen
60
Fulton
60
Madison
60
St. Joseph
60
Bartholomew
48
Gibson
42
Marion
54
Scott
36
Benton
60
Grant
54
Marshall
60
Shelby
54
Blackford
60
Greene
54
Martin
48
Spencer
36
Boone
54
Hamilton
54
Miami
60
Starke
60
Brown
48
Hancock
54
Monroe
48
Steuben
60
Carroll
60
Harrison
36
Montgomery
60
Sullivan
54
Cass
60
Hendricks
54
Morgan
48
Switzerland
42
Clark
36
Henry
54
Newton
60
Tippecanoe
60
Clay
54
Howard
60
Noble
60
Tipton
60
Clinton
54
Huntington
60
Ohio
42
Union
48
Crawford
36
Jackson
48
Orange
42
Vanderburgh
36
Daviess
48
Jasper
60
Owen
54
Vermillion
60
Dearborn
48
Jay
60
Parke
60
Vigo
60
Decatur
48
Jefferson
42
Perry
36
Wabash
60
Dekalb
60
Jennings
48
Pike
42
Warren
60
Delaware
60
Johnson
54
Porter
60
Warrick
36
Dubois
42
Knox
48
Posey
42
Washington
36
Elkhart
60
Kosciusko
60
Pulaski
60
Wayne
54
Fayette
54
LaGrange
60
Putnam
54
Wells
60
Floyd
36
Lake
60
Randolph
54
White
60
Fountain
60
LaPorte
60
Ripley
48
Whitley
60
(e) In addition to the liquid holding capacity of a dosing tank stated in section 62(f) of this rule the following shall apply:
(1) If the effluent force main drains to the soil absorption system, or if it does not drain between doses, the dose volume shall be the DDF.
(2) If the effluent force main drains back to the dosing tank, the dose volume shall be the DDF plus the volume contained in the effluent force main.
(f) The distal end of the effluent force main in the distribution box must be fitted with an elbow turned down or a sanitary tee, or else the distribution box must be baffled.
(g) The minimum inside diameter of the effluent force main shall be one (1) inch. The maximum inside diameter of the effluent force main shall be four (4) inches.
(h) Tables IX and X, as follows, shall be used in determining friction losses in the effluent force mains and manifold when plastic pipe is used:
Table IX – Friction Losses in Plastic Pipe (per 100 feet of pipe)
Pipe Diameter, Flow (gpm), Velocity (v)2, and Friction Loss Head (Hf)1
Flow (gpm)
1"
1 1/4"
1 1/2"
2"
2 1/2"
3"
4"
Q
v
Hf
v
Hf
v
Hf
v
Hf
v
Hf
v
Hf
v
Hf
1
0.37
0.11
2
0.74
0.38
0.43
0.10
3
1.11
0.78
0.64
0.21
0.47
0.10
4
1.49
1.31
0.86
0.35
0.63
0.16
5
1.86
1.92
1.07
0.52
0.79
0.24
6
2.23
2.70
1.29
0.71
0.95
0.33
0.57
0.10
8
2.97
4.59
1.72
1.19
1.26
0.56
0.77
0.17
10
3.71
6.90
2.15
1.78
1.58
0.83
0.96
0.25
0.67
0.11
15
5.57
14.7
3.22
3.76
2.37
1.74
1.43
0.52
1.01
0.22
20
7.43
25.2
4.29
6.42
3.16
2.96
1.91
.87
1.34
0.37
0.87
0.13
25
9.28
38.6
5.37
9.74
3.94
4.46
2.39
1.29
1.68
0.54
1.09
0.19
30
6.44
13.6
4.73
6.27
2.87
1.81
2.01
0.76
1.30
0.26
35
7.51
18.2
5.52
8.40
3.35
2.42
2.35
1.01
1.52
0.35
0.88
0.10
40
8.59
23.6
6.30
10.7
3.83
3.12
2.68
1.28
1.74
0.44
1.01
0.12
45
7.09
13.5
4.30
3.85
3.02
1.54
1.95
0.55
1.13
0.15
50
7.88
16.5
4.78
4.68
3.35
1.93
2.17
0.67
1.26
0.18
60
9.47
23.6
5.74
6.62
4.02
2.72
2.60
0.94
1.51
0.25
70
6.70
8.86
4.69
3.67
3.04
1.25
1.76
0.33
80
7.65
11.5
5.36
4.69
3.47
1.59
2.02
0.42
90
8.60
14.3
6.03
5.83
3.91
1.99
2.27
0.52
100
6.70
7.13
4.34
2.42
2.52
0.63
125
8.38
10.9
5.43
3.72
3.15
0.96
150
6.51
5.16
3.78
1.34
175
7.60
6.90
4.41
1.79
200
8.68
8.93
5.04
2.27
225
5.67
2.84
250
6.30
3.37
275
6.93
4.13
300
7.56
4.87
325
8.19
5.70
1 This figure is based on flows for PVC Schedule 40 pipe (flow coefficient: C-150). Other values for friction loss may be used if documentation from the pipe manufacturer is provided with the plan submittal. Calculations using the Hazen-Williams equation may be used if provided with the plan submittal.
2 Flow velocity must be at least 2 fps; flow velocities above 5 fps should be avoided.
Table X - Plastic Pipe Fittings: Friction Loss - Equivalent Length of Straight Pipe (ft.)*
Fitting:
1"
1 1/4"
1 1/2"
2"
2 1/2"
3"
4"
90° elbow, standard sharp, inside radius
5.3
6.7
7.5
8.6
9.3
11.1
13.1
90° elbow, long sweep radius
2.5
3.8
4.0
5.7
6.9
7.9
12.0
45° elbow, standard
1.4
1.8
2.1
2.6
3.1
4.0
5.1
Tee Flow (run flow)
1.7
2.3
2.7
4.3
5.1
6.2
8.3
Tee Flow (branch flow)
6.0
7.0
8.0
12.0
15.0
16.0
22.0
Gate Valve
0.6
0.8
1.0
1.5
1.6
2.0
3.0
Male/Female adapter
2.0
2.8
3.5
4.5
5.5
6.5
9.0
*Assigned values. Other values for friction loss may be used if documentation from the pipe manufacturer is provided with the plan submittal.
(Indiana State Department of Health; 410 IAC 6-8.3-76; filed Oct 19, 2012, 2:06 p.m.: 20121114-IR-410120156FRA; filed Apr 9, 2014, 9:51 a.m.: 20140507-IR-410130350FRA)