Indiana Administrative Code (Last Updated: December 20, 2016) |
Title 410. INDIANA STATE DEPARTMENT OF HEALTH |
Article 410IAC33. INDOOR AIR QUALITY |
Rule 410IAC33-4. IAQ Criteria for Schools |
Section 410IAC33-4-4. Temperature and relative humidity
-
(a) Heating facilities shall be capable of and shall be operated to maintain a temperature during periods of student occupancy not less than the following:
(1) Sixty-eight (68) degrees Fahrenheit (F) in all:
(A) instructional rooms;
(B) offices;
(C) locker rooms; and
(D) cafeterias.
(2) Sixty-five (65) degrees Fahrenheit in activity rooms and shops.
(3) Sixty (60) degrees Fahrenheit in interior toilet rooms.
(b) Where provided air-conditioning systems shall be capable of providing and shall be operated to maintain a temperature not to exceed seventy-eight (78) degrees Fahrenheit and sixty-five percent (65%) relative humidity during periods of student occupancy. (Indiana State Department of Health; 410 IAC 33-4-4; filed Apr 13, 2011, 11:18 a.m.: 20110511-IR-410090682FRA)