Indiana Administrative Code (Last Updated: December 20, 2016) |
Title 327. WATER POLLUTION CONTROL DIVISION |
Article 327IAC3. WASTEWATER TREATMENT FACILITIES; ISSUANCE OF PERMITS; CONSTRUCTION AND PERMIT REQUIREMENTS |
Rule 327IAC3-6. Technical Standards for Sanitary Collection Systems |
Section 327IAC3-6-21. Lift station valve requirements
-
(a) Lift stations shall be provided with shutoff valves and check valves that are operable from the floor level.
(b) Shutoff valves and check valves shall be in accordance with the following:
(1) Shutoff valves shall be placed on the suction line of dry pit pumps.
(2) Shutoff valves and check valves shall be placed on the discharge line of each pump that is not a screw pump.
(3) The check valve shall be:
(A) located between the shutoff valve and the pump;
(B) suitable for the material being handled;
(C) placed on the horizontal portion of the discharge piping except for ball check valves; and
(D) rated for the normal pressure and water hammer.
(Water Pollution Control Division; 327 IAC 3-6-21; filed May 17, 1999, 12:11 p.m.: 22 IR 3096; readopted filed Apr 11, 2005, 2:45 p.m.: 28 IR 2470; readopted filed Jun 15, 2011, 11:15 a.m.: 20110713-IR-327110193BFA)