Indiana Administrative Code (Last Updated: December 20, 2016) |
Title 327. WATER POLLUTION CONTROL DIVISION |
Article 327IAC8. PUBLIC WATER SUPPLY |
Rule 327IAC8-3.2. Technical Standards for Water Mains |
Section 327IAC8-3.2-17. Installation
-
(a) All water mains and their accessories shall be installed and pressure and leak tested in accordance with the applicable provisions of one (1) of the following:
(1) C600-99 AWWA Standard for Installation of Ductile-Iron Water Mains and Their Appurtenances.
(2) C602-00 AWWA Standard for Cement-Mortar Lining of Water Pipelines in Place, 4 in (100 mm) and Larger.
(3) C603-96(R00) AWWA Standard for Installation of Asbestos Cement Pressure Pipe.
(4) C605-94 AWWA Standard for Underground Installation of Polyvinyl Chloride (PVC) Pressure Pipe and Fittings for Water.
(5) C606-04 Grooved and Shouldered Joints.
If an AWWA Standard is not available for the particular installation, the manufacturer’s recommended installation procedure shall be followed.
(b) Continuous and uniform bedding shall be provided in the trench for all buried pipe. Backfill material shall be tamped in layers around the pipe and to a sufficient height above the pipe to adequately support and protect the pipe. All stones unable to pass through a U.S. Standard Sieve opening of two (2) inches that are found in the trench within six (6) inches of the outside edge of the pipe shall be removed.
(c) All necessary reaction blocking, tie rods, or joints designed to prevent movement for pipes and fittings (regardless of material type) at tees, bends, plugs, and hydrants shall be installed to prevent movement in conformance with AWWA Standard C600-99.
(d) Water mains shall be covered with earthen cover in accordance with the following:
Depth of Cover Requirements for Water Mains
County
Cover[1] (in)
Adams
60
Allen
60
Bartholomew
48
Benton
60
Blackford
60
Boone
54
Brown
48
Carroll
60
Cass
60
Clark
36
Clay
54
Clinton
54
Crawford
36
Daviess
48
Dearborn
48
Decatur
48
Dekalb
60
Delaware
60
Dubois
42
Elkhart
60
Fayette
54
Floyd
36
Fountain
60
Franklin
48
Fulton
60
Gibson
42
Grant
60
Greene
54
Hamilton
54
Hancock
54
Harrison
36
Hendricks
54
Henry
54
Howard
60
Huntington
60
Jackson
48
Jasper
60
Jay
60
Jefferson
42
Jennings
48
Johnson
54
Knox
48
Kosciusko
60
LaGrange
60
Lake
60
LaPorte
60
Lawrence
48
Madison
60
Marion
54
Marshall
60
Martin
48
Miami
60
Monroe
48
Montgomery
60
Morgan
48
Newton
60
Noble
60
Ohio
42
Orange
42
Owen
54
Parke
60
Perry
36
Pike
42
Porter
60
Posey
42
Pulaski
60
Putnam
54
Randolph
54
Ripley
48
Rush
54
St. Joseph
60
Scott
36
Shelby
54
Spencer
36
Starke
60
Steuben
60
Sullivan
54
Switzerland
42
Tippecanoe
60
Tipton
60
Union
48
Vanderburgh
36
Vermillion
60
Vigo
60
Wabash
60
Warren
60
Warrick
36
Washington
36
Wayne
54
Wells
60
White
60
Whitley
60
[1] The cover dimension is measured from the top of pipe to the proposed finish grade.
(Water Pollution Control Division; 327 IAC 8-3.2-17; filed Mar 31, 1999, 1:50 p.m.: 22 IR 2506; errata filed Aug 30, 1999, 12:06 p.m.: 23 IR 25; readopted filed Jan 10, 2001, 3:23 p.m.: 24 IR 1518; filed Apr 24, 2006, 3:00 p.m.: 29 IR 2956; readopted filed Nov 21, 2007, 1:16 p.m.: 20071219-IR-327070553BFA; readopted filed Jul 29, 2013, 9:21 a.m.: 20130828-IR-327130176BFA)