Section 675IAC22-2.5-9. Chapter 8; interior finish, decorative materials and furnishings


Latest version.
  •    Chapter 8 is amended as follows: (a) Amend Section 803.4 to delete the text and insert as follows: The required flame spread or smoke developed index of interior finish and trim surfaces in existing buildings shall be allowed to be achieved by application of approved fire retardant coatings, paints, or solutions having a flame spread index exceeding that allowed. Such applications shall comply with NFPA 703 and the required fire retardant properties shall be maintained or renewed in accordance with the manufacturer's instructions.

      (b) Amend Section 804.3 to delete "and existing" without substitution.

      (c) Delete Section 805.4 in its entirety without substitution.

      (d) Add Section 806.1.4 to read as follows: 806.1.4. A natural cut tree. At least two (2) days prior to placing a natural cut tree in a public building the fire department having jurisdiction shall be notified.

      (e) Amend Section 807.1.2 to delete the second exception without substitution.

      (f) Delete Section 808.2 in its entirety without substitution. (Fire Prevention and Building Safety Commission; 675 IAC 22-2.5-9; filed Aug 1, 2014, 11:01 a.m.: 20140827-IR-675130341FRA, eff Dec 1, 2014)