Section 675IAC22-2.5-17. Chapter 24; flammable finishes  


Latest version.
  •    Chapter 24 is amended as follows: (a) Delete Section 2401.3 in its entirety without substitution.

      (b) Amend Section 2404.3.2.5, in Exception 1 and Exception 2, to delete "adequately" without substitution.

      (c) Amend Section 2405.3.2 as follows: