Section 675IAC20-5-20. Electrical, mechanical, and illumination requirements  


Latest version.
  •    (a) The requirements of 675 IAC 17, the Indiana Electrical Code, shall be followed for the wiring, grounding, bonding, and installation of electrical equipment and metallic appurtenances to the water attraction.

      (b) Artificial lighting shall be provided for all water attractions to be used indoors or water attractions used during periods of darkness. The lighting shall be sufficient to make a six (6) inch black disc, placed on a white background clearly visible from the side of the water attraction when that disc is placed on the floor of the water attraction.

      (c) Mechanical equipment shall be designed and installed in accordance with the requirements of 675 IAC 18, the Indiana Mechanical Code. Corrosion-resistant fan and ductwork shall be installed in the enclosed disinfectant chemical feed room or rooms.

      (d) Heaters shall be installed and tested to comply with the requirements under the 675 IAC 25, Indiana Fuel Gas Code for gas applications or 675 IAC 17, the Indiana Electrical Code for electrical applications.

      (e) Overhead clearance shall be the same as for swimming pools as found in the Indiana Electrical Code (675 IAC 17). (Fire Prevention and Building Safety Commission; 675 IAC 20-5-20; filed Mar 25, 2011, 10:19 a.m.: 20110420-IR-675090789FRA; readopted filed Aug 7, 2013, 8:51 a.m.: 20130904-IR-675130181RFA)