Indiana Administrative Code (Last Updated: December 20, 2016) |
Title 675. FIRE PREVENTION AND BUILDING SAFETY COMMISSION |
Article 675IAC15. INDUSTRIALIZED BUILDING SYSTEMS |
Rule 675IAC15-2. Indiana Mobile Structures Code |
Section 675IAC15-2-64. Horizontal vent connections and grade
-
(a) Horizontal Vents. Each vent shall extend vertically from its fixture "T" above the extreme flood level of the fixture it is venting before offsetting horizontally or being connected with any other vent pipe. Vents for horizontal drains shall connect above the centerline of the drain piping ahead of the trap.
(b) Grade. Vents shall be designed to drain back to the drainage system by gravity. (Fire Prevention and Building Safety Commission; 675 IAC 15-2-64; filed Mar 25, 1986, 1:44 pm: 9 IR 2001, eff Jun 15, 1986; readopted filed Nov 29, 2001, 12:21 p.m.: 25 IR 1306; readopted filed Sep 21, 2007, 9:20 a.m.: 20071010-IR-675070388RFA; readopted filed Oct 10, 2007, 9:16 a.m: 20071031-IR-675070388RFA; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA)