Section 675IAC15-2-14. Design load deflection  


Latest version.
  •    When a structural assembly is subjected to total design live loads, the deflection for structural framing members shall not exceed the following:

    Floor

    L/240

    Roof and Ceiling

    L/180

    Headers, Beams, Girders

    L/180 (Vertical Loads Only)

     

    Where L = the clear span between supports or two times the length of a cantilever.

    (Fire Prevention and Building Safety Commission; 675 IAC 15-2-14; filed Mar 25, 1986, 1:44 pm: 9 IR 1984, eff Jun 15, 1986; readopted filed Nov 29, 2001, 12:21 p.m.: 25 IR 1306; readopted filed Sep 21, 2007, 9:20 a.m.: 20071010-IR-675070388RFA; readopted filed Oct 10, 2007, 9:16 a.m: 20071031-IR-675070388RFA; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA)