Section 675IAC14-4.3-282. Circulation piping  


Latest version.
  •    Section S4213 Circulation piping is added as follows:

    (1) S4213.1 Circulation system piping, other than that integrally included in the manufacture of the pool, shall be subject to an induced static hydraulic pressure test (sealed system) at twenty-five (25) pounds per square inch for thirty (30) minutes. This test shall be performed before the deck is poured, and the pressure shall be maintained through the deck pour.

    (2) S4213.2 Valves installed in or under any decks shall provide a minimum ten (10) inches diameter access cover and valve pit to facilitate servicing.

    (3) S4213.3 A hose bibb with a vacuum breaker shall be provided for washing down the entire deck area.