Section 675IAC14-4.3-242. Section E3807.7; cables  


Latest version.
  •    (a) At the end of item 6, in the exception, delete ", the applicable article".

      (b) After item 6 of the exception, add item 7 and Table E3807.8 to read as follows: The allowable cable fill shall not exceed that permitted by Table E3807.8. A multiconductor cable having two or more conductors shall be treated as a single conductor for calculating the percentage of conduit fill area. For cables that have elliptical cross sections, the cross-sectional area calculation shall be based on the major diameter of the ellipse as a circle diameter.

    TABLE E3807.8

    PERCENT OF CROSS SECTION OF CONDUIT AND TUBING FOR CONDUCTORS


    NUMBER OF CONDUCTORS

    MAXIMUM PERCENT OF CONDUIT AND TUBING AREA FILLED BY CONDUCTORS

    1

    53

    2

    31

    Over 2

    40

    (Fire Prevention and Building Safety Commission; 675 IAC 14-4.3-242; filed Jun 13, 2005, 3:00 p.m.: 28 IR 3300, eff 90 days after filing with the Secretary of State; filed Oct 21, 2005, 1:50 p.m.: 29 IR 810; filed Mar 6, 2008, 11:13 a.m.: 20080402-IR-675070483FRA; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA)