Indiana Administrative Code (Last Updated: December 20, 2016) |
Title 675. FIRE PREVENTION AND BUILDING SAFETY COMMISSION |
Article 675IAC14. ONE AND TWO FAMILY DWELLING CODE |
Rule 675IAC14-4.3. 2005 Indiana Residential Code |
Section 675IAC14-4.3-233.5. Section E3802.7; bar sink receptacles
Latest version.
-
5. (a) In the title of SECTION E3802.7, before "bar sink receptacles", insert "laundry, utility, and wet".
(b) Change the first sentence of SECTION E3802.7 to read as follows: All 125-volt, single-phase, 15- and 20-ampere receptacles that are installed within 6 feet of the outside edge of a laundry, utility, or wet bar sink shall have ground-fault circuit-interrupter protection for personnel. (Fire Prevention and Building Safety Commission; 675 IAC 14-4.3-233.5; filed Oct 21, 2005, 1:50 p.m.: 29 IR 809; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA)