Indiana Administrative Code (Last Updated: December 20, 2016) |
Title 675. FIRE PREVENTION AND BUILDING SAFETY COMMISSION |
Article 675IAC14. ONE AND TWO FAMILY DWELLING CODE |
Rule 675IAC14-4.3. 2005 Indiana Residential Code |
Section 675IAC14-4.3-216. Section E3501.6.2; service disconnect location
-
At the end of SECTION E3501.6.2, add a sentence to read as follows: Conductors shall be considered outside of a building or structure under any of the following conditions:
(1) where installed under not less than 2 inches (51 mm) of concrete beneath a building or other structure,
(2) where installed within a building or other structure in a raceway that is encased in concrete or brick not less than 2 inches thick, or
(3) where installed in conduit and under not less than 18 inches (457 mm) of earth beneath a building or other structure.
(Fire Prevention and Building Safety Commission; 675 IAC 14-4.3-216; filed Jun 13, 2005, 3:00 p.m.: 28 IR 3297, eff 90 days after filing with the Secretary of State; filed Oct 21, 2005, 1:50 p.m.: 29 IR 807; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA)