Section 675IAC14-4.3-145.5. Section M1411.4; insulation of refrigerant piping
-
5. Change Section M1411.4 as follows:
(1) Change the number of Section M1411.4 to read as follows: Section M1411.5 insulation of refrigerant piping.
(2) Add Section M1411.4 to read as follows: M1411.4 auxiliary drain pan. Category IV condensing appliances shall have an auxiliary drain pan when installed over a finished ceiling. These pans shall be installed in accordance with the applicable provisions of Section M1411.3.
Exception: Fuel-fired appliances that automatically shut down operation in the event of a stoppage in the condensate drainage system.