Section 675IAC18-1.6-11. Chapter 11; refrigeration  


Latest version.
  •    (a) Delete Section 1101.10 in its entirety without substitution.

      (b) Amend Section 1105.6.3 by inserting after "multispeed fans shall be allowed to be", the words "30 air changes per hour".

      (c) Amend Section 1106.5 to read as follows: Remote controls. Where flammable refrigerants are used, remote control of the mechanical equipment and appliances located in the machinery room shall comply with Sections 1106.5.1 and 1106.5.2 shall be provided at an approved location immediately outside the machinery room and adjacent to its principal entrance. (Fire Prevention and Building Safety Commission; 675 IAC 18-1.6-11; filed Aug 1, 2014, 11:20 a.m.: 20140827-IR-675130340FRA, eff Dec 1, 2014)