Section 675IAC16-1.4-8. Chapter 7; sanitary drainage  


Latest version.
  •    Chapter 7 is amended as follows:

    (a) Amend Table 704.1 as follows: delete "0.083.3 mm/m" and insert "83.3 mm/m".

    (b) Amend Section 705.8.2 as follows: delete "purple" and "not purple in color and," without substitution.

    (c) Amend Table 702.2 as follows: under "Copper or copper alloy tubing", delete without substitution "M or DWV".

    (d) Amend Section 705.14.2 as follows: delete "purple" and "not purple in color and" without substitution.

    (e) Amend Section 706.3 as follows: after "combination fittings", delete "side inlets or".

    (f) Delete the fourth sentence in Section 708.3.5 without substitution.

    (g) Amend Table 710.1(2) as follows: In the second column, delete "2,900" and insert "3,900".

    (h) Add Section 710.3 to read as follows: 710.3 Minimum underground drainage size. The minimum pipe size installed underground in a sanitary drainage system within a building shall be two (2) inch nominal (50.8 mm) pipe size.

    (Fire Prevention and Building Safety Commission; 675 IAC 16-1.4-8; filed Sep 25, 2012, 2:42 p.m.: 20121024-IR-675110448FRA, eff 90 days after filing with the Publisher)