Section 327IAC3-6-27. Wet wells  


Latest version.
  •    (a) The effective volume of a wet well shall not be greater than the volume created by the average daily flow in thirty (30) minutes.

      (b) The floor of a wet well shall have a minimum slope of forty-five (45) degrees to a hopper bottom.

      (c) A wet well that is covered shall be vented to allow for the displacement of air due to the filling of the wet well. (Water Pollution Control Division; 327 IAC 3-6-27; filed May 17, 1999, 12:11 p.m.: 22 IR 3097; readopted filed Apr 11, 2005, 2:45 p.m.: 28 IR 2470; readopted filed Jun 15, 2011, 11:15 a.m.: 20110713-IR-327110193BFA)