Section 326IAC7-4-4. Wayne County sulfur dioxide emission limitations  


Latest version.
  •    The following sources and facilities located in Wayne County shall comply with the sulfur dioxide emission limitations in pounds per million Btu, unless otherwise specified, and other requirements:

     

    Source

    Facility Description

    Emission Limitations

     

    (1) Belden Corp.

    Boilers 3,4,5,6 (oil) (common stack)

    1.6

     

    (2) Earlham College

    Boilers 1 & 2 (oil/gas) (common stack)

    1.6

     

    (3) Johns-Manville Co.

    Boiler B-2 (oil/gas)

    1.6

     

     

    Glass Furnaces SX-2,SX-3 (common stack)

    9 pounds per ton

     

    (4) Joseph Hill (Plant A)

    Boilers 1,2,4 (oil) (common stack)

    1.6

     

     

    Boiler 3 (oil)

    1.6

     

    (5) Joseph Hill (Plant B)

    Boilers 1,2,3 (oil/gas) (common stack)

    0.3

     

    (6) Kemper

    Boiler 1 (coal)

    2.3

     

     

    Boiler 2 (wood/coal)

    2.1

     

     

    Boiler 3 (wood/sawdust)

    1.2

    Kemper Boilers 1 and 2 also shall be limited to one and three-tenths (1.3) pounds per million Btu, and Boiler 3 also shall be limited to one and two-tenths (1.2) pounds per million Btu based on the annual average sulfur content of the fuel over any twelve (12) consecutive month period.

     

    (7) NATCO

    Boiler 1 (coal)

    4.9

    NATCO Boiler 1 also shall be limited to three and seven-tenths (3.7) pounds per million Btu based on the annual average sulfur content of the fuel over any twelve (12) consecutive month period.

     

    (8) Ralston Purina Co.

    Boilers 1 & 2 (oil/gas) common stack)

    1.6

     

    (9) Richmond Power and Light (RP&L)

    Boilers 1 and 2 (coal) (common stack)

    6.0

    RP&L shall construct a new good engineering practice stack with height of at least three hundred twenty-five (325) feet above grade by July 31, 1988.

     

    (10) Richmond State Hospital

    Boilers 1,2,3,4 (coal) (common stack)

    6.0

     

    (11) Sanyo E&E

    Boiler 1 (coal)

    4.9

     

     

    Boiler 2 (coal)

    4.9

    Sanyo E&E Boilers 1 and 2 also shall be limited to three and nine-tenths (3.9) pounds per million Btu based on the annual average sulfur content of the fuel over any twelve (12) consecutive month period.

     

    (12) Wallace Metals

    Boiler 1 (oil/gas)

    1.6

    (Air Pollution Control Division; 326 IAC 7-4-4; filed Aug 28, 1990, 4:50 p.m.: 14 IR 73; readopted filed Jan 10, 2001, 3:20 p.m.: 24 IR 1477)