Section 326IAC2-9-14. Internal combustion sources  


Latest version.
  •    (a) Any stationary internal combustion source, including any combination of turbines, reciprocating engines, or engines, may elect to comply with this section by complying with section 1 of this rule and limiting fuel usage for every twelve (12) month period to less than the limits found in:

    (1) subsection (e), Table 1 for a single fuel or a combination of two (2) fuels; or

    (2) subsection (f), Table 2 for a single fuel or a combination of two (2) fuels.

      (b) Sources electing to comply with subsection (a)(1) must be able to demonstrate compliance not later than thirty (30) days after receipt of a written request by the department or U.S. EPA. No other demonstration of compliance shall be required. A source specific operating agreement is not required for these sources.

      (c) Sources electing to comply with subsection (a)(2) must:

    (1) comply with the requirements of section 1 of this rule; and

    (2) submit a request for a source specific operating agreement.

      (d) For sources complying with subsection (a)(2), the following records shall be kept at the source:

    (1) Monthly hours operated for each combustion unit.

    (2) Records of annual fuel usage for each combustion unit.

    (3) Routine maintenance records.

      (e) Table 1 limits shall be as follows:

    TABLE 1

    Fuel

    Maximum Fuel Usage per Year

    Large turbine

     

    Natural gas

    227.27 MMCF/yr

    Distillate

    1,414.42 kgal/yr

    Uncontrolled natural gas prime movers

     

    Gas turbines

    294.11 MMCF/yr

    2-cycle lean burn

    37.03 MMCF/yr

    4-cycle lean burn

    31.25 MMCF/yr

    4-cycle rich burn

    43.47 MMCF/yr

    Diesel, reciprocating

     

    <600 HP

    165.51 kgal/yr

    Gasoline, reciprocating

     

    <250 HP

    12.26 kgal/yr

    Diesel, large stationary

    235.45 kgal/yr

    Unit abbreviations:

     

    kgal = 103 gallons

     

    MMCF = 106 cubic feet

     

      (f) Table 2 limits shall be as follows:

    TABLE 2

    Fuel

    Maximum Fuel Usage per Year

    Large turbine

     

    Natural gas

    363.63 MMCF/yr

    Distillate

    2,263.07 kgal/yr

    Uncontrolled natural gas prime movers

     

    Gas turbines

    470.58 MMCF/yr

    2-cycle lean burn

    59.25 MMCF/yr

    4-cycle lean burn

    50.00 MMCF/yr

    4-cycle rich burn

    69.56 MMCF/yr

    Diesel, reciprocating

     

    <600 HP

    264.82 kgal/yr

    Gasoline, reciprocating

     

    <250 HP

    19.62 kgal/yr

    Diesel, large stationary

    376.72 kgal/yr

    Unit abbreviations:

     

    kgal = 103 gallons

     

    MMCF = 106 cubic feet

     

    (Air Pollution Control Division; 326 IAC 2-9-14; filed May 7, 1997, 4:00 p.m.: 20 IR 2315; readopted filed Oct 22, 2004, 10:35 a.m.: 28 IR 814; filed Sep 28, 2011, 10:56 a.m.: 20111026-IR-326070286FRA; filed Feb 6, 2012, 2:54 p.m.: 20120307-IR-326090493FRA)