Section 170IAC6-3-27. Station flow temperature table  


Latest version.
  •    Table A.

    TABLE A

    Station Flow Temperatures

    Outside Temperature

    Degrees Fahrenheit

    Day Schedule

    Permissible Night Schedules

    6:00 a.m. to 6:00 p.m.

    6:00 p.m. to 9:30 p.m.

    3:30 a.m. to 6:00 a.m.

    9:30 pm. to 3:30 a.m.

    70

    85

    90

    75

    65

    97

    103

    87

    60

    109

    115

    99

    55

    120

    125

    110

    50

    130

    135

    120

    45

    139

    144

    129

    40

    148

    152

    139

    35

    156

    160

    148

    30

    164

    167

    158

    25

    171

    174

    167

    20

    178

    179

    176

    15

    185

    185

    185

    10

    190

    190

    190

    5

    195

    195

    195

    zero

    200

    200

    200

    -5

    203

    203

    203

    -10

    206

    206

    206

    -15

    208

    208

    208

    -20

    210

    210

    210

    NOTE.─In case of difficulty in maintaining the average temperatures with these flow temperatures, increase the rate of pumpage.

    (Indiana Utility Regulatory Commission; No. 17689: Standards of Service For Central Station Hot Water Heating Utilities Table A; filed Jan 2, 1946, 10:00 am: Rules and Regs. 1947, p. 1669; readopted filed Jul 11, 2001, 4:30 p.m.: 24 IR 4233; readopted filed Apr 24, 2007, 8:21 a.m.: 20070509-IR-170070147RFA; readopted filed Aug 2, 2013, 2:16 p.m.: 20130828-IR-170130227RFA)